TI402F/00/en/07.06
Technical Information
Tank Side Monitor NRF590
Inventory Control
Field device for tank sensor operation and monitoring and for
integration into inventory control systems
Software Version 02.03.
Application
The Tank Side Monitor NRF590 is a sensor integration
and monitoring unit for bulk storage tank gauging
applications.
It can be used with Micropilot level radars and combined
with other HART compatible devices.
The Tank Side Monitor offers the following functions:
intrinsically safe (i.s.) power supply of the connected
devices
parametrization of the connected devices
display of the measured values
tank calculations for accurate correction of the tank
distortions
Features and benefits
i.s. power supply and communication for
Micropilot M/S and Levelflex M level radars
Connects up to 6 HART devices via i.s. 2 wire, for
example Prothermo for average temperature
measurement and Cerabar/Deltabar for HTMS
density applications
Backlit graphical LCD display; operation via 3 optical
keys (touch control)
User-friendly operating menu (multi-lingual)
Interfaces to FuelsManager SCADA tank inventory
system via RTU 8130
Provides communication to PLC, DCS and SCADA
systems
Various industry standard communication protocols,
including
Sakura V1
EIA-485 Modbus
Whessoematic WM 550
BPM (compatible with Enraf systems)
Approved for use in explosion hazardous areas
Weights & Measure-approved for use in custody
transfer applications
Vista de pagina 0
1 2 3 4 5 6 ... 39 40

Indice de contenidos

Pagina 1 - Tank Side Monitor NRF590

TI402F/00/en/07.06Technical InformationTank Side Monitor NRF590Inventory ControlField device for tank sensor operation and monitoring and for integrat

Pagina 2 - Table of Contents

10Values transmitted by the Field ProtocolsThe following values can be transmitted by the communication protocols:Tank Value Symbol V1 - old V1 - new

Pagina 3 - Function and system design

11Technical data of the non-IS inputs and outputsAnalogue 4...20 mA input (option, s. pos. 20 of the product structure)Analogue 4...20 mA outputsDiscr

Pagina 4

12Technical Data of the IS inputs and outputsHART input loopSpot RTD input (option, s. pos. 40 of the product structure)IS Analogue 4...20 mA input (o

Pagina 5 - Typical Tank calculations

13Auxiliary energyAC supply 55 ... 264 VAC; insensitive to polarity / CSA approved: 55 ... 250 VACDC supply 18 ... 55 VAC/DCPower consumption • 370 mA

Pagina 6 - P3 Position

14Electrical connection - non-i.s. terminalsTerminal assignment of the field protocol/host sideL00-NRF590-04-08-08-en-00204 A1/+05 A2/-06 B1/+07 B2/-0

Pagina 7

15Terminal01L/+02N/-04A1/+05A2/-06B1/+07B2/-00SPower supplyDiscrete I/O A +Discrete I/O A-Discrete I/O B +Discrete I/O B-Cable screen08C109C210C311C41

Pagina 8 - Inputs and outputs

16Connection of the field protocolsSakura V1The V1 protocol provides 2 wire communication allowing up to 10 devices to operate on a loop. V1 connects

Pagina 9

17Connection of the auxiliary energyThe Tank Side Monitor can be AC or DC supplied, depending on the installed power supply board. The AC supply needs

Pagina 10 - Field Protocols

18Electrical connection - i.s. terminalsTerminal assignmentL00-NRF590-04-00-08-en-018Terminal Designation Meaning16 D+ + RTD drive1)1) These terminal

Pagina 11

19Connection of HART instrumentsTank sensorsThe Tank Side Monitor can interface to a maximum of 6 i.s. HART sensors. All HART sensors are connected to

Pagina 12

2Table of ContentsFunction and system design. . . . . . . . . . . . . . . . . . . . . 3Application . . . . . . . . . . . . . . . . . . . . . . . . . .

Pagina 13 - Tank Ground

20Performance characteristicsAccuracy HART sensorsAccuracy of all data from connected HART sensors depends on the type and installation of instruments

Pagina 14 - Standard (not certified)

21Installation conditionsWall mountingL00-NRF590-17-00-06-xx-001Mounting on vertical railL00-NRF590-17-00-06-en-0023.94"(100 mm)3.94"(100 mm

Pagina 15

22Mounting on horizontal railL00-NRF590-17-00-06-en-003Rail mounting kit(Order No.: 52013134)maximumØ3.5" (90 mm)

Pagina 16

23Ambient conditionsAmbient temperature -40 °C ... +60 °C (-40 °F ... +140 °F )Storage temperature -55 °C ... 85 °C (-67 °F...185 °F)Ingress protectio

Pagina 17 - L00-NRF590-04-00-08-en-004

24Mechanical constructionDesign, dimensionsL00-NRF590-06-00-06-yy-001Construction The NRF590 housing has three separate compartments, one containing a

Pagina 18 - Terminal assignment

25Human interfaceDisplay and operating elementsLiquid crystal display (LCD)Four lines with 20 characters each. Display contrast adjustable through key

Pagina 19 - Tank Side Monitor

26Format of decimal numbersThe number of decimal places displayed can be selected from three resolution presets (high, normal, low)VAlue resolution pr

Pagina 20 - Performance characteristics

27Operating concept The Tank Side Monitor is operated via a four-layer menu. The structure of the menu accounts for typical measuring tasks as well as

Pagina 21 - Installation conditions

28Certificates and ApprovalsCE mark The measuring system meets the legal requirements of the EC-guidelines. Endress+Hauser confirms the instrument pas

Pagina 22 - Ø3.5" (90 mm)

29External standards and guidelinesEN 60529Protection class of housing (IP-code)EN 61010Safety regulations for electrical devices for measurement, con

Pagina 23 - Ambient conditions

3Function and system designApplication The Tank Side Monitor NRF590 is a field device for the integration of tank sensors into tank inventory systems.

Pagina 24 - Mechanical construction

30Ordering informationProduct structure Ordering structure Tank Side Monitor NRF59010 CertificatesA For non-hazardous areas6 ATEX II 2 (1) EEx d (ia)

Pagina 25 - Human interface

3180 Glands/Entries - non ISF 2 x G 1/2" gland (in preparation)B 2 x Ex d M20x1.5 entriesC 2 x Ex d G 1/2" entriesD 2 x Ex d 1/2" NPT e

Pagina 26 - Format of decimal numbers

32AccessoriesDiscrete I/O modules Standard mechanical diagram for all I/O modulesL00-NRF590-00-00-08-en-0011.00(25.4).25(6.35).040 (1.0) DIA..30(7.6).

Pagina 27 - L00-NRF590-07-00-00-en-004

33Output modulesAC voltage DC voltageNRF590 order code1)module A1) This order code is valid if the module is preinstalled in the Tank Side Monitor as

Pagina 28 - Certificates and Approvals

34Input modulesAC voltage DC voltageNRF590 order code1)module A1) This order code is valid if the module is preinstalled in the Tank Side Monitor as

Pagina 29

35Relay output moduleNRF590 order code1)module A1) This order code is valid if the module is preinstalled in the Tank Side Monitor as module A or mod

Pagina 30 - Ordering information

36Rail mounting kit For rail mounting the Tank Side Monitor to vertical or horizontal pipe.Order-Number: 52013134L00-NRF590-00-00-06-en-001

Pagina 31 - 110 Additional options

37Supplementary DocumentationSpecial Documentation SD 001VSpecial Documentation - Radar Tank GaugingTechnical Information TI 006GTechnical Information

Pagina 34

4HART interfacePower supply for HART instrumentsThe Tank Side Monitor provides intrinsically safe power for 2-wire tank sensors. It also can provide i

Pagina 35

International Head QuarterEndress+HauserGmbH+Co. KGInstruments InternationalColmarer Str. 679576 Weil am RheinDeutschlandTel. +49 76 21 9 75 02Fax +49

Pagina 36 - Order-Number: 52013134

5Typical Tank calculationsSetup preset Installation example Sensors measured/calculated valuesrequired parametersDirect level measurementLevel onlyL00

Pagina 37 - Supplementary Documentation

6Setup preset Installation example Sensors measured/calculated valuesrequired parametersHydrostatic Tank Gauging (HTG)HTG P1L00-NRF590-14-00-08-yy-006

Pagina 38

7Corrections The Tank Side Monitor can automatically calculate the following corrections:• Correction for the Hydrostatic Tank Deformation (HyTD)• Tem

Pagina 39

8Inputs and outputsL00-NRF590-04-08-08-en-003Non IS inputs and outputsIS inputs and outputs4...20 mA4...20 mA 4...20 mA4...20 mANon-i.s.terminalsEx dP

Pagina 40 - International Head Quarter

9Fieldbus Protocols The Tank Side Monitor NRF590 supports all of the following industry standard communication protocols allowing it to be integrated