8300 8315 L&J Tankway Software Description
4.9.2 Application
The Emulator point (EMU) provides a communication interface between older tank
gauging system and point blocks within the TankGate. Currently, the TankGate can
emulate a Whessoe Varec Model 6810 Tank Scanning Unit (TSU).
The EMU point associates a tank gauge point with an address to by used by TankView.
EMU.0 provides point references for TankView System Addresses 1-50. EMU.1 is
associated with System Addresses 51-100. A EMUGW gateway point is automatically
created when the protocol for a COM point is set to TSU Slave.
Dynamic Parameters Function
PntStatus
Byte value indicating status of point Values are:
Dynamic ParametersFunction
PntStatusByte value indicating status of point Values are:
0: No error
15: Invalid Type for PntRef
16 Invalid Number for PntRef
17 Invalid Param for PntRef
19: PntRef point does not exist
25: PntRef is not defined
PntCheckSum
CRC-16 Checksum for point's static Configuration parameters.